Air conditioner of Switch Cabinet
When the power consumption is 500W,
When the temperature difference between inside and outside is 15℃ and the surface area is
4.6㎡, 55.3Kcal/hr/㎡ x 4.6㎡ = 254Kcal/h
| Temperature Differential (℃) | (kcal/h/㎡) | (BTU/h/㎡) |
|---|---|---|
| 5 | 16.7 | 66.3 |
| 10 | 42.2 | 167.4 |
| 15 | 55.3 | 219.4 |
| 20 | 92.2 | 365.8 |
| 25 | 116.7 | 463.1 |
| 30 | 142.2 | 564.2 |
| 35 | 166.9 | 662.3 |
Control panel volume(W x H x D) - 800 x 1600 x 500,
[The method of calculating the surface area control panel(in the case of installing on the factory floor)]
: (0.8m x 1.6m x 2EA) + (1.6m x 0.5m x 2EA) + (0.8m x 0.5m x 1EA) = 4.6㎡
| Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
|---|---|---|
| Transformer |
Rated Capacity
|
· Smaller in size leads to more Heat Loss Rate |
| Voltage Control Unit | Approximately 10% of Rated Capacity | · Heat Loss |
| Heavy Resistor, Fixed, Variable | Approximately 1/3 of Rated Capacity | - |
| Constant-Voltage Switch | Approximately 10~15% of Rated Capacity | · Heat Loss |
| UPS |
|
|
| Switching Regulator | Approximately 30~55% of Rated Output |
|
| Low-Tension Condenser | Approximately 0.2% of Rated Output | · Rated Capacity KVA. (100V, 60HZ,1KVA = 256.3㎌) |
| Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
|---|---|---|
| AC SERVO AMP |
Rated Capacity
|
|
| POWER UNIT | Approximately 3~5% of Rated Capacity |
|
| Inverter | Approximately 3~5% of Rated Capacity |
|
| Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
|---|---|---|
| Factory Computer | 1unit : Approximately 100~300W | - |
| CRT | 1unit : Approximately 60~130W | · Vary according to size(inch) |
| Flopppy Disc | 2unit of 3.5~5inches :20W | - |
| Fixed Disc | 10~20 M byte 100 | · Power Supply |
| Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
|---|---|---|
| NFB, LEB |
(NBF) Rated Capacity
NBF+5W Approximately 20W(Leakage From Electronic Circuits) |
|
| Electro-Magnetic Relay |
Rated Capacity
|
|
| Thermal Relay |
Rated Capacity
|
· When Applying Maximum Static Capacity |
| Relay | Approximately 5W | · When Applying Maximum Static Capacity |
| Machinery Installed In Panel | Heat Loss-general Standards |
|---|---|
| Compact Relay | 1unit : Approximately 1~2W (NFB) |
| SSC, SSR | Using Current X Approximately 1.6W |
| Thermost at Meter |
|
| Machinery Installed In Panel | Heat Loss-general Standards |
|---|---|
| Fan Moter |
|